Core Capabilities & Features
1. PowerControl & PowerAssist
PowerControl lets you set a maximum grid or generator current, using surplus power for battery charging without risking an overload. PowerAssist goes further, drawing on the battery to cover peak demand and recharging once the load eases.
2. Two AC Outputs
The main output switches over seamlessly during a grid failure, keeping critical loads running without disruption. A second output stays live only while AC input is present, ideal for loads you don’t want draining the battery.
3. ESS-Ready with Anti-Islanding
Built-in anti-islanding functionality and a growing list of country approvals make the MultiPlus-II suited to Energy Storage System applications. It carries all the standard MultiPlus features plus extended PowerControl and PowerAssist capability via an external current sensor.
4. Parallel & Three-Phase Expansion
Connect up to 6 units in parallel, or configure three units for three-phase output, to scale power as your system grows. Six sets of three can combine for a 75 kW / 90 kVA inverter with over 1200 Amps of charging capacity.
Technical Specifications
| Parameter | Specification |
| DC Input Voltage Range | 38–66 V |
| Cont. Output Power at 25°C | 4000 W / 5000 VA |
| Cont. Output Power at 40°C | 3700 W |
| Cont. Output Power at 65°C | 3000 W |
| Peak Power | 9000 W |
| Maximum Efficiency | 96% |
| Max. Battery Charge Current | 70 A |
| Charge Voltage ‘Absorption’ | 57.6 V |
| Charge Voltage ‘Float’ | 55.2 V |
| Max. AC Input Current | 50 A |
| Transfer Switch Rating | 50 A |
| Auxiliary Output | 50 A |
| Operating Temperature Range | -40 to +65 °C |
| Protection Category | IP22 |
| Weight | 30 kg |
| Dimensions (H x W x D) | 565 x 320 x 149 mm |







Reviews